P55-4

Minimum Rating
50.0 kVA / 40.0 kW

Maximum Rating
55.0 kVA / 44.0 kW

Emissions/Fuel Strategy
Fuel Optimised


SKU: 5f17b06bb887 Categories: ,

Full Specifications

Generator Set Specifications

Minimum Rating 50.0 kVA / 40.0 kW
Maximum Rating 55.0 kVA / 44.0 kW
Emissions/Fuel Strategy Fuel Optimised
50 Hz Prime 50.0 kVA / 40.0 kW
50 Hz Standby 55.0 kVA / 44.0 kW
60 Hz Prime – / –
Frequency 50 Hz
Speed 1500 RPM
Voltage 240-415 Volts
50 Hz Prime Rating These ratings are applicable for supplying continuous electrical power (at variable load) in lieu of commercially purchased power. There is no limitation to the annual hours of operation and this model can supply 10% overload power for 1 hour in 12 hours.
60 Hz Prime Rating These ratings are applicable for supplying continuous electrical power (at variable load) in the event of a utility power failure. No overload is permitted on these ratings. The alternator on this model is peak continuous rated (as defined in ISO 8528-3).
50 Hz Standby Rating Standard reference conditions 25�C (77�F) Air Inlet Temp, 100m (328 ft) A.S.L. 30% relative humidity. Fuel consumption data at full load with diesel fuel with specific gravity of 0.85 and conforming to BS2869: 1998, Class A2.

Engine Specifications

Engine Model Perkins® 1104C-44TG2/3
Bore 105 mm (4.1 in)
Stroke 127 mm (5 in)
Governor Type Mechanical
Displacement 4.4l (268.5 cu. in)
Compression Ratio 18.2:1

Benefits & Features

FG Wilson Diesel Engine

Perkins Engine

Alternator

Benefiting from a choice of leading alternators, the range incorporates the Marelli alternator as standard across three phase models.

DCP-10

The FG Wilson DCP range allows you to monitor and control your generator set with ease, providing important diagnostic information whilst ensuring your unit operates within safe parameters. FG Wilson DCP digital control panels, provide simple, intuitive menu navigation and control of your generator set operations. Key information is displayed via the LCD screen and LED’s using universally recognised symbols, eliminating the need for complex instructions or language settings.

Design Criteria

Prime Rating These ratings are applicable for supplying continuous electrical power (at variable load) in lieu of commercially purchased power. There is no limitation to the annual hours of operation and this model can supply 10% overload power for 1 hour in 12 hours. Standby Rating These ratings are applicable for supplying continuous electrical power (at variable load) in the event of a utility power failure. No overload is permitted on these ratings. The alternator on this model is peak continuous rated (as defined in ISO 8528-3). Standard Reference Conditions Note: Standard reference conditions 25°C (77°F) Air Inlet Temp, 100m (328 ft) A.S.L. 30% relative humidity. Fuel consumption data at full load with diesel fuel with specific gravity of 0.85 and conforming to BS2869: 1998, Class A2.

Single-Source Supplier

Fully prototype tested with certified torsional vibration analysis available

World Wide Product Support

FG Wilson manufactures product in the following locations: Northern Ireland • Brazil • China • India • USA With headquarters in Northern Ireland, FG Wilson operates through a Global Dealer Network.

Optional Equipment

Exhaust

  • Industrial, Residential, Critical Silencers

Alternator

  • Alternator options including 3 Phase sensing, quadrature droop kit and PMG
  • Anti-Condensation Heater and Panel Circuitry (AH1)

Control Panels

  • PowerWizard 1.1+ Control Panel (PWT1.1+)
  • PowerWizard 2.1 Control Panel (PWT2.1)

Starting/Charging

  • Static battery charger with auto boost for lead acid battery

General

  • Upgrade to Standard Set for “CE” Certification
  • EEC Declaration of Conformity
  • Narrow, Wide or Skid Base
  • Sound attenuated, steel or galvanised enclosure
  • Dual wall fuel tanks

Standard Equipment

Engine

  • Air Cleaner
  • Lube oil drain valve
  • Engine filled with lubrication oil
  • High Coolant Temperature Shutdown
  • Low Oil Pressure Shutdown
  • Exhaust stub pipe and gasket

Cooling

  • Radiator & Cooling Fan
  • Fan,fan drive and battery charging alternator drive fully guarded to meet EC Machinery Directive
  • Cooling System filled with Coolant mix
  • Coolant drain valve

Exhaust

  • Exhaust flange outlet
  • Exhaust stub pipe and gasket

Fuel

  • 8 Hr Fuel Tank
  • Customer connection fuel sockets

Alternator

  • Marelli
  • SHUNT Excitation
  • IP23 Protection

Control Panel

  • DCP-10 / PowerWizard 1.1

Mounting

  • Base, Formed Steel with Single wall Fuel Tank
  • Certified Base Mounted Lifting Eyes, and Rear Drag Eyelets
  • Battery Tray and Cables
  • Anti-vibration mounts