P450-3

Minimum Rating

400.0 kVA / 320.0 kW

Maximum Rating

450.0 kVA / 360.0 kW

Emissions/Fuel Strategy

Standard reference conditions 25°C (77°F) Air Inlet Temp, 100m (328 ft) A.S.L. 30% relative humidity. Fuel consumption data at full load with diesel fuel with specific gravity of 0.85 and conforming to BS2869: 1998, Class A2.


SKU: efa444e5750a Categories: ,

Full Specifications

Generator Set Specifications

Minimum Rating 400 kVA / 320 kW
Maximum Rating 450 kVA / 360 kW
Emissions/Fuel Strategy Fuel Optimised
50 Hz Prime 400 kVA / 320 kW
50 Hz Standby 450 kVA / 360 kW
Frequency 50 Hz
Speed 1500 RPM
Voltage 220-415 Volts

Engine Specifications

Engine Model Perkins® 2206A-E13TAG3
Bore 130.0 mm (5.1 in)
Stroke 157.0mm (6.2 in)
Governor Type Electronic
Displacement 12.5l (762.8 cu. in)
Compression Ratio 16.3:1

Benefits & Features

FG Wilson Diesel Engine

Perkins Engine

Alternator

Benefiting from a choice of leading alternators, the range incorporates the FG Wilson alternator as standard.

Design Criteria

Prime Rating These ratings are applicable for supplying continuous electrical power (at variable load) in lieu of commercially purchased power. There is no limitation to the annual hours of operation and this model can supply 10% overload power for 1 hour in 12 hours. Standby Rating These ratings are applicable for supplying continuous electrical power (at variable load) in the event of a utility power failure. No overload is permitted on these ratings. The alternator on this model is peak continuous rated (as defined in ISO 8528-3). Standard Reference Conditions Note: Standard reference conditions 25°C (77°F) Air Inlet Temp, 100m (328 ft) A.S.L. 30% relative humidity. Fuel consumption data at full load with diesel fuel with specific gravity of 0.85 and conforming to BS2869: 1998, Class A2.

Single-Source Supplier

Fully prototype tested with certified torsional vibration analysis available

World Wide Product Support

FG Wilson manufactures product in the following locations: Northern Ireland • Brazil • China • India • USA With headquarters in Northern Ireland, FG Wilson operates through a Global Dealer Network.

PowerWizard 1.1+

The FG Wilson PowerWizard range of digital control panels, combine straightforward menu navigation with advanced metering and protection technology. They are used in automatic mains failure applications in conjunction with transfer panels. Our PowerWizard range allows you to monitor and control your generator set with ease, whilst ensuring your unit operates within safe parameters and provides important diagnostic information when needed.

Optional Equipment

Exhaust

  • Industrial, Residential, Critical Silencers

Alternator

  • Quadrature Droop Kit (AR6)
  • Anti-Condensation Heater and Panel Circuitry (AH1)
  • AREP / PMG excitation
  • AVR Upgrades
  • Three phase sensing
  • Oversize Alternator
  • Coastal ingress protection alternator
  • Leroy Somer Alternator

Control Panels

  • PowerWizard 2.1
  • easYgen-2500

Starting/Charging

  • Heavy duty dry battery
  • Battery charger with auto boost

General

  • Upgrade to Standard Set for “CE” Certification
  • EEC Declaration of Conformity
  • Dual wall base tank (8 hrs)
  • Sound attenuated or High ambient enclosures
  • Battery isolator switch

Standard Equipment

Engine

  • Air Cleaner
  • Lube oil drain valve
  • Engine filled with lubrication oil
  • High Coolant Temperature Shutdown
  • Low Oil Pressure Shutdown
  • Engine mounted battery charging alternator

Cooling

  • Package mounted radiator
  • Radiator fan and charging alternator guards
  • Coolant Drain Valve
  • Cooling System filled with Coolant mix

Exhaust

  • Exhaust flange outlet
  • Exhaust bellows and gasket

Fuel

  • 8 Hr Fuel Tank
  • BSP Fuel Sockets

Alternator

  • FG Wilson
  • SHUNT Excitation
  • IP21 Protection

Control Panel

  • PowerWizard 1.1+

Mounting

  • Robust steel constructed base frame
  • Base frame drag and lift points
  • Captive linear vibration isolators between base and engine-generator
  • Battery Tray and Cables