F275-1

Minimum Rating

250.0 kVA / 200.0 kW

Maximum Rating

275.0 kVA / 220.0 kW

Emissions/Fuel Strategy

Fuel Optimised


SKU: 03de5911fd0b Categories: , ,

Specifications

Overview

Utilising the proven and trusted FG Wilson generator set design, the 8.5 – 290 kVA range provides power that is uncompromising on quality with the introduction of FG Wilson engines and a simplified choice of options. The FG Wilson engines provide reliable power suitable for nonregulated markets or non-mobile applications. Combined with the Marelli alternator, providing coastal insulation protection and a RFI filter as standard, a trusted performance is guaranteed.

Generator Set Specifications

Minimum Rating 250.0 kVA / 200.0 kW
Maximum Rating 275.0 kVA / 220.0 kW
Voltage 220-415 Volts
Frequency 50 Hz
Speed 1500 RPM
50 Hz Prime Rating 250.0 kVA / 200.0 kW
50 Hz Standby Rating 275.0 kVA / 220.0 kW
60 Hz Prime Rating – / –
60 Hz Standby Rating – / –

Generator Set Configurations

Emissions/Fuel Strategy Fuel Optimised

Engine Specifications

Engine Model FG Wilson FD6-10.3A1
Bore 123.0 mm (4.8 in)
Displacement 10.3l (630.9 cu .in.)
Stroke 145.0 mm (5.7 in)
Compression Ratio 16.8:1
Governor Type Electronic

Benefits & Features

FG Wilson Diesel Engine

FG Wilson Alternator

DCP-10 Control Panel

The FG Wilson DCP range allows you to monitor and control your generator set with ease, providing important diagnostic information whilst ensuring your unit operates within safe parameters. FG Wilson DCP digital control panels, provide simple, intuitive menu navigation and control of your generator set operations. Key information is displayed via the LCD screen and LED’s using universally recognised symbols, eliminating the need for complex instructions or language settings.

Design Criteria

Prime Rating These ratings are applicable for supplying continuous electrical power (at variable load) in lieu of commercially purchased power. There is no limitation to the annual hours of operation and this model can supply 10% overload power for 1 hour in 12 hours. Standby Rating These ratings are applicable for supplying continuous electrical power (at variable load) in the event of a utility power failure. No overload is permitted on these ratings. The alternator on this model is peak continuous rated (as defined in ISO 8528-3). Standard Reference Conditions Note: Standard reference conditions 25°C (77°F) Air Inlet Temp, 100m (328 ft) A.S.L. 30% relative humidity. Fuel consumption data at full load with diesel fuel with specific gravity of 0.85 and conforming to BS2869: 1998, Class A2.

Single-Source Supplier

Fully prototype tested with certified torsional vibration analysis available

World Wide Product Support

FG Wilson manufactures product in the following locations: Northern Ireland • Brazil • China • India • USA With headquarters in Northern Ireland, FG Wilson operates through a Global Dealer Network.

Equipment

F275-1Standard Equipment

Air Inlet

  • Air Cleaner

Cooling

  • Cooling system filled with coolant mix
  • Radiator and Cooling Fan

Exhaust

  • Exhaust stub pipe & gasket

Fuel

  • 8Hr fuel tank

Alternator

  • IP23 Protection
  • FG Wilson.com

Control Panel

  • DCP-10

Mounting

  • Anti-vibration mounts
  • Base, formed steel with single wall fuel tank
  • Certified base mounted lifting eyes, and rear drag eyelets

Power

  • 3 Pole circuit breaker

General

  • Generating set is load tested and all protective devices and control functions are simulated and checked

F275-1Optional Equipment

Alternator

  • Anti-condensation heater

Power Termination

  • 4 Pole Circuit Breaker

Starting/Charging

  • Lead-Acid Battery (Dry)

General

  • CE Certification
  • Neutral Earth Link
  • CAL Steel Enclosure