P55-6S

Minimum Rating
50.0 kVA / 50.0 kW

Maximum Rating
55.0 kVA / 55.0 kW

Emissions/Fuel Strategy
EU Stage IIIA emissions compliant.


SKU: 583544ebc163 Categories: ,

Full Specifications

Generator Set Specifications

Minimum Rating 50.0 kVA / 50.0 kW
Maximum Rating 55.0 kVA / 55.0 kW
Emissions/Fuel Strategy EU Stage IIIA emissions compliant.
50 Hz Prime 50.0 kVA / 50.0 kW
50 Hz Standby 55.0 kVA / 55.0 kW
60 Hz Prime – / –
Frequency 50 Hz
Speed 1500 RPM
Voltage 220-240 Volts
50 Hz Prime Rating These ratings are applicable for supplying continuous electrical power (at variable load) in lieu of commercially purchased power. There is no limitation to the annual hours of operation and this model can supply 10% overload power for 1 hour in 12 hours.
60 Hz Prime Rating These ratings are applicable for supplying continuous electrical power (at variable load) in the event of a utility power failure. No overload is permitted on these ratings. The alternator on this model is peak continuous rated (as defined in ISO 8528-3).
50 Hz Standby Rating Standard reference conditions 25�C (77�F) Air Inlet Temp, 100m (328 ft) A.S.L. 30% relative humidity. Fuel consumption data at full load with diesel fuel with specific gravity of 0.85 and conforming to BS2869: 1998, Class A2.

Engine Specifications

Engine Model Perkins® 1104D-44TG2/3
Bore 105 mm (4.1 in)
Stroke 127 mm (5 in)
Governor Type Mechanical
Displacement 4.4l (268.5 cu. in)
Compression Ratio 18.23:1