Full Specifications

Generator Set Specifications

Minimum Rating 6.8 kVA / 6.8 kW
Maximum Rating 8.8 kVA / 8.8 kW
Emissions/Fuel Strategy EUIIIa Emissions Compliant
50 Hz Prime 6.8 kVA / 6.8 kW
50 Hz Standby 7.5 kVA / 7.5 kW
60 Hz Prime 8.0 kVA / 8.0 kW
60 Hz Standby 8.8 kVA / 8.8 kW
Frequency 50 / 60 Hz
Speed 1500 or 1800 RPM
Voltage 220-240 Volts
50 Hz Prime Rating These ratings are applicable for supplying continuous electrical power (at variable load) in lieu of commercially purchased power. There is no limitation to the annual hours of operation and this model can supply 10% overload power for 1 hour in 12 hours.
60 Hz Prime Rating These ratings are applicable for supplying continuous electrical power (at variable load) in the event of a utility power failure. No overload is permitted on these ratings. The alternator on this model is peak continuous rated (as defined in ISO 8528-3).
50 Hz Standby Rating Standard reference conditions 25�C (77�F) Air Inlet Temp, 100m (328 ft) A.S.L. 30% relative humidity. Fuel consumption data at full load with diesel fuel with specific gravity of 0.85 and conforming to BS2869: 1998, Class A2.

Engine Specifications

Engine Model Perkins® 403D-11G
Bore 81.0 mm (3.0 in)
Stroke 81.0 mm (3.2 in)
Governor Type Mechanical
Displacement 1.1l (69.0 cu. in)
Compression Ratio 23:01

Benefits & Features

Engine

  • Air Cleaner
  • Lube oil drain valve
  • Engine filled with lubrication oil
  • High Coolant Temperature Shutdown
  • Low Oil Pressure Shutdown

Cooling

  • Package mounted radiator
  • Radiator & Cooling Fan
  • Coolant Drain Valve
  • Fan, Fan drive and battery charging Alternator drive fully guarded to meet EC Machinery Directive
  • Cooling System filled with Coolant mix

Exhaust

  • Exhaust flange outlet
  • Exhaust stub pipe and gasket

Fuel

  • 8 Hr Fuel Tank or Skidbase
  • Fuel Fittings for Local and Remote Feed

Alternator

  • Leroy Somer
  • SHUNT Excitation
  • IP23 Protection

Control Panel

  • DCP-10 / DeepSea DSE 4520

Mounting

  • Base, Formed Steel with Skid base or Single wall Fuel Tank
  • Certified Base Mounted Lifting Eyes, and Rear Drag Eyelets
  • Anti-vibration mounts
  • Battery Tray and Cables

Optional Equipment

Exhaust

  • Industrial, Residential, Critical Silencers

Alternator

  • Quadrature Droop Kit (AR6)
  • Anti-Condensation Heater and Panel Circuitry (AH1)

Control Panels

  • PowerWizard 1.1 Control Panel (PWT1.1)
  • PowerWizard 1.1+ Control Panel (PWT1.1+)
  • PowerWizard 2.1 Control Panel (PWT2.1)
  • Deep Sea DSE7420

Starting/Charging

  • Lead Acid battery (Dry)

General

  • Upgrade to Standard Set for “CE” Certification
  • EEC Declaration of Conformity
  • Narrow, Wide or Skid Base
  • Sound attenuated, steel or galvanised enclosure
  • Dual wall fuel tanks

Standard Equipment

Engine

  • Air Cleaner
  • Lube oil drain valve
  • Engine filled with lubrication oil
  • High Coolant Temperature Shutdown
  • Low Oil Pressure Shutdown

Cooling

  • Package mounted radiator
  • Radiator & Cooling Fan
  • Coolant Drain Valve
  • Fan, Fan drive and battery charging Alternator drive fully guarded to meet EC Machinery Directive
  • Cooling System filled with Coolant mix

Exhaust

  • Exhaust flange outlet
  • Exhaust stub pipe and gasket

Fuel

  • 8 Hr Fuel Tank or Skidbase
  • Fuel Fittings for Local and Remote Feed

Alternator

  • Leroy Somer
  • SHUNT Excitation
  • IP23 Protection

Control Panel

  • DCP-10 / DeepSea DSE 4520

Mounting

  • Base, Formed Steel with Skid base or Single wall Fuel Tank
  • Certified Base Mounted Lifting Eyes, and Rear Drag Eyelets
  • Anti-vibration mounts
  • Battery Tray and Cables