PRO60-2
Minimum Rating
60 KVA / 47.2 KW
Maximum Rating
60 KVA / 48 KW
Frequency
EU3a Emissions Compliant
Full Specifications
Generator Set Specifications
Engine Specifications
Optional Equipment
Exhaust
- Industrial, Residential, Critical Silencers
Alternator
- Permanent Magnet Generator (PMG)
- Anti-condensation heater 110 or 230 VAC
Starting/Charging
- 12V battery charger
- UL/CSA listed 120 V, 20 Amp battery charger, shock mounted and enclosed in dust proof housing
General
- CE socket box with integrated MCB and RCBO protection
- Clipsal socket box with integrated MCB and RCBO protection
- Coolant heater 110 or 230 VAC
- CE labelling (also available for BSFC)
Standard Equipment
Engine
- Air Cleaner
- Lube oil drain valve
- Engine filled with lubrication oil
- High Coolant Temperature Shutdown
- Low Oil Pressure Shutdown
Cooling
- Cooling package mounted radiator with high ambient capability
- Pusher fan with guards
- Coolant drain line with internal brass ball control valve piped to base-frame
- Low coolant level shutdown.
- 50% coolant antifreeze with corrosion inhibitor
Exhaust
- Integrated spark arresting silencer with flexible connectors, in separate compartment
Fuel
- 301L double wall fuel tank, 24 hr runtime @ 75% prime rating
- Auxiliary connections for customer supplied fuel transfer with 3 way fuel transfer system, internally mounted within the bunded area.
Alternator
- Leroy Somer
- SHUNT Excitation
- IP23 Protection
Control Panel
Mounting
- Generator set soft mounted using captive vibration mounts
- Heavy duty steel base frame contains integral double wall fuel tank
- Provides 110% spill containment of all engine fluids
- Forklift pockets and heavy duty drag bar with skid plates