CM20151208 29446 18805 1

P250-5

Minimum Rating 230.0 kVA / 184.0 kW
Maximum Rating 250.0 kVA / 200.0 kW
Emissions/Fuel Strategy Standard reference conditions 25°C (77°F) Air Inlet Temp, 100m (328 ft) A.S.L. 30% relative humidity. Fuel consumption data at full load with diesel fuel with specific gravity of 0.85 and conforming to BS2869: 1998, Class A2.
Request a Quote

Generator Set Specifications

Minimum Rating
230.0 kVA / 184.0 kW
Maximum Rating
250.0 kVA / 200.0 kW
Emissions/Fuel Strategy
Standard reference conditions 25°C (77°F) Air Inlet Temp, 100m (328 ft) A.S.L. 30% relative humidity. Fuel consumption data at full load with diesel fuel with specific gravity of 0.85 and conforming to BS2869: 1998, Class A2.
50 Hz Prime
230 kVA / 184 kW
50 Hz Standby
250 kVA / 200 kW
60 Hz Prime
60 Hz Standby
Frequency
50 Hz
Speed
1500 RPM
Voltage
115-400 Volts
50 Hz Prime Rating
60 Hz Prime Rating
50 Hz Standby Rating

Engine Specifications

Engine Model
Perkins® 1506A-E88TAG2
Bore
112.0 mm (4.4 in)
Stroke
149.0 mm (5.9 in)
Governor Type
Electronic
Displacement
8.8 (57.0 cu. in)
Compression Ratio
16.1:1

The Story

The 6.8 – 25 kVA range of generator sets is designed to power your every need. With an enhanced choice of power nodes, this range is engineered for optimum performance in diverse applications including construction, residential, retail and telecommunications. The contemporary design of the polymer enclosure option redefines durability in the marketplace and further enhances this range alongside the more traditional metal enclosure. For a life without interruptions, trust FG Wilson.

Industry Leading Perkins Engine

The 400 Series engines offer highly competitive performance, fuel economy and EUIIIa Emissions compliance on selected nodes. These engines have been designed to be reliable and to offer low cost of ownership in the wide variety of markets they serve.

Alternator

Benefiting from the well-established Leroy Somer alternator, known worldwide for providing power generation expertise and solutions offering longlife products with low maintenance

Deep Sea DSE4520

The DSE4520 is a compact Auto Mains (Utility) Failure Control Module that has been developed to provide an outstanding range of features within a compact enclosure. Monitoring engine speed, oil pressure, coolant temperature, frequency, voltage, current, power and fuel level, the modules will give comprehensive engine and alternator protection. This will be indicated on a large back-lit LCD icon display via an array of warning, electrical trip and shutdown alarms.

Single-Source Supplier

Fully prototype tested with certified torsional vibration analysis available

World Wide Product Support

FG Wilson manufactures product in the following locations: Northern Ireland • Brazil • China • India With headquarters in Northern Ireland, FG Wilson operates through a Global Dealer Network.

Standard Reference Conditions

Prime Rating – These ratings are applicable for supplying continuous electrical power (at variable load) in lieu of commercially purchased power. There is no limitation to the annual hours of operation and this model can supply 10% overload power for 1 hour in 12 hours. Standby Rating – These ratings are applicable for supplying continuous electrical power (at variable load) in the event of a utility power failure. No overload is permitted on these ratings. The alternator on this model is peak continuous rated (as defined in ISO 8528-3). Note: Standard reference conditions 25°C (77°F) Air Inlet Temp, 100m (328 ft) A.S.L. 30% relative humidity. Fuel consumption data at full load with diesel fuel with specific gravity of 0.85 and conforming to BS2869: 1998, Class A2.

Optional Equipment

Exhaust
  • Industrial, Residential, Critical Silencers
Alternator
  • Upgrade to Leroy Somer Alternator
  • Quadrature Droop Kit
  • Anti-Condensation Heater and Panel Circuitry (AH1)
Control Panels
  • PowerWizard 2.1+ Control Panel (PWT2.1)
  • EasYgen 2500 control panel
Starting/Charging
  • Lead Acid battery (Dry)
General
  • Upgrade to Standard Set for "CE" Certification
  • Compact Skid Base for Open Sets
  • Sound attenuated, steel or galvanised enclosure

Standard Equipment

Engine
  • Air Cleaner
  • Lube oil drain valve
  • Engine filled with lubrication oil
  • High Coolant Temperature Shutdown
  • Low Oil Pressure Shutdown
Cooling
  • Coolant Drain Valve
  • Fan, Fan drive and battery charging Alternator drive fully guarded to meet EC Machinery Directive
  • Cooling System filled with Coolant mix
  • Radiator and Cooling Fan
Exhaust
  • Exhaust stub pipe and gasket
Fuel
  • 8 Hr Fuel Tank
  • Fuel Fittings for Local and Remote Feed
Alternator
  • Marelli
  • SHUNT Excitation
  • IP23 Protection
  • Coastal Insulation Protection
Control Panel
  • PowerWizard 1.1+
Mounting
  • Base, Formed Steel with Single wall Fuel Tank
  • Certified Base Mounted Lifting Eyes, and Rear Drag Eyelets